ATRT-01 S3 Transformer Turns Ratio Tester
----------部分中文介紹產(chǎn)品已停產(chǎn)或參數(shù)有變更,內(nèi)容僅供參考。

ATRT-01 S3

Transformer Turns Ratio Tester

Part Number(s)
9023-UC [ATRT-01 S3]
Download Links
ATRT-01 S3 Datasheet (English)
ATRT-01/01B S3 User's Manual (English)

The ATRT-01 S3 is Vanguard’s fourth generation, micro-processor based, single phase, automatic transformer turns-ratio tester. The ATRT-01 S3 uses the measuring method to determine the transformer turns-ratio. The transformer turns-ratio is determined by precisely measuring the voltages across the unloaded transformer windings. The ATRT-01 S3’s measuring circuitry self adjusts before each measurement to ensure turns-ratio accuracy. Two selectable test voltages, 4Vac and 40Vac, offer flexibility in testing different types of transformers.

  • Standalone or computer-controlled
  • Inexpensive
  • Displays turns-ratio from 0.8-15,000
  • Calculates turns-ratio percentage error
  • Displays winding polarity and phase angle
  • Displays excitation current

ATRT-01 S3

Cables

Cable Part Number
[8000-0006] RS-232C Cable 8000-0006
[8000-0093] H and X Cable Set 8000-0093
[8000-0112] Power Cable 8000-0112

ATRT-01 S3

Technical Specifications

TYPE Transformer Turns Ratio Tester
PHYSICAL SPECIFICATIONS Dimensions: 12” x 10” x 8” (30.4 cm x 25.4 cm x 20.3 cm)
Weight: 8 lbs. (3.6 Kg)
INPUT POWER 120 or 240 Vac (Selectable), 50/60 Hz
MEASURING METHOD
RATIO MEASURING RANGE 0.8 - 15,000 (5 digit resolution)
TURNS-RATIO ACCURACY 40 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (1%)
4 Vac: 0.8-1,999 (0.1%), 2,000-3,999 (0.25%), 4,000-15,000 (2%)
TEST VOLTAGE 4 Vac @ 1.0A, 40 Vac @ 0.6A
PHASE ANGLE MEASUREMENT 0 - 360 degrees, Accuracy ±0.2 degree (±1 digit)
POLARITY READING In-Phase or Out-of-Phase indication
EXCITATION CURRENT READING RANGE 0-2 Amperes, Accuracy: 2% of reading (±1 mA)
DISPLAY Back-lit LCD (128 x 64 pixels), viewable in direct sunlight and low light levels
COMPUTER INTERFACE RS-232C
PC SOFTWARE Windows XP/Vista/7 Transformer Analysis Software (included with purchase)
INTERNAL TEST RECORD STORAGE 128 records of 33 readings
EXTERNAL TEST RECORD STORAGE Up to 999 test records on external USB Flash drive.
SAFETY
ENVIRONMENT Operating: -10oC to 50oC (15oF to +122oF)
Storage: (-30oC to 70oC (-22oF to +158oF)
HUMIDITY (MAX) 90% RH @ 40 C (104 F) non-condensing
ALTITUDE (MAX) 2000m (6562 ft) to full safety specifications
CABLES One 15 ft. (4.6m) Single phase cable, one power cord, one cable bag
OPTIONS Transportation Case (Can hold unit and cables)
WARRANTY One year on parts and labor
Specifications are valid at nominal voltage and ambient temperature of +25C (+77F).