ATRT-03 S2
|
3-Phase Transformer Turns Ratio Tester
|
|
|
|
|
|
|
|
Part Number(s)
9003-UC [ATRT-03 S2]
9003-PR [Printer Option]
Download Links
|
The Vanguard Instruments ATRT-03 S2 is the third generation, microprocessor-based, automatic, three phase, transformer turns-ratio tester. This light weight, rugged, portable unit is designed for transformer testing at utility power substations.
The ATRT-03 S2 determines the transformer turns ratio using the measurement method. The ATRT-03 S2 outputs an excitation test voltage to the transformer primary windings. The induced secondary voltage is sensed and the transformer turns ratio is calculated. The ATRT-03 S2 is capable of measuring turns ratios from 0.8 to 15,000. The transformer turns-ratio, excitation current, and phase angle readings are displayed on the large LCD. The automatic transformer type detection feature allows the ATRT-03 S2 to detect and test 130 transformer types defined by . |
- Highest ratio: 0.8 - 15,000
- Capable of detecting 130 different 3-phase transformer types defined by
- 3 Test voltages available: 8Vac, 40Vac, 100Vac
- Phase angle and excitation current measuring
- Computer Interface (RS-232C and USB Port)
- USB flash drive interface
- Name-plate turns ratio calculation
- Computed % error based on measured and calculated ratio
- Optional 4.5" thermal printer
- Powered from a single phase 100-264 Vac 50/60 Hz
|
|
|
|
|
|
|
ATRT-03 S2
|
Cables
|
|
|
|
|
|
|
|
|
|
|
|
|
ATRT-03 S2
|
Technical Specifications
|
|
|
|
|
|
|
TYPE |
Portable, lightweight, automatic, 3-phase transformer turns-ratio meter |
PHYSICAL SPECIFICATIONS |
18”W x 7”H x 15”D (45.7 cm x 17.8 cm x 38.1 cm); Weight: 20 lbs (9.0 kg) |
OPERATING VOLTAGE |
100 – 240 Vac, 50/60 Hz |
MEASUREMENT METHOD |
|
TURNS-RATIO MEASURING RANGE |
0.8 – 15,000 |
TURNS-RATIO ACCURACY |
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 15,000: ±1% @ 8 Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 15,000: ±1% @ 40 Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 15,000: ±1% @ 100 Vac |
TEST VOLTAGES |
8 Vac @ 1Amp, 40 Vac @ 0.2 Amp, 100 Vac @ 0.1 Amp |
EXCITATION CURRENT READING RANGE |
0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA) |
PHASE-ANGLE MEASUREMENT |
0 – 360 Degrees; Accuracy: ±0.2 degree (±1 digit) |
DISPLAY |
Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels |
PRINTER |
Built-in 4.5-inch wide thermal printer |
COMPUTER INTERFACES |
One RS-232C port, One USB port |
EXTERNAL DATA STORAGE |
One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included). |
PC SOFTWARE |
Windows XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price |
INTERNAL TEST RECORD STORAGE |
Can store 112 transformer test records internally. Each record holds the test record header and up to 33 readings. |
INTERNAL TEST PLAN STORAGE |
Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the RS-232C/USB port or via the USB Flash drive interface |
LOAD TAP CHANGER CONTACT |
240 Vac, 2 Amps |
SAFETY |
|
ENVIRONMENT |
Operating: -10 to 50 C (15 to +122 F); Storage: -30 C to 70 C (-22 to +158 F) |
CABLES |
One 15-foot Single-phase set, One 15-foot 3-phase set, One 25-foot extension set, One safety ground, One USB, One RS-232C, cable bag |
OPTIONS |
Transportation Case |
WARRANTY |
One year on parts and labor |
Specifications are valid at nominal voltage and ambient temperature of +25C (+77F).